Issue: Tank 02 (บ่อเก็บน้ำใต้ดิน-K) percentage recalibration — InfluxDB discontinuity

  • Date: 2026-06-30T14:20+07:00
  • GitHub issue: racksync/obh-iot#1
  • Status: Done (change applied & verified) — follow-ups open
  • Area: Water system / Node-RED / InfluxDB / Grafana
  • Owner: RACKSYNC (Damrongwit)

The underground K tank (tank 02 / Basement K, friendly name บ่อเก็บน้ำใต้ดิน-K) level gauge capped at ~93% and never reached 100%. Root cause: the % is computed in Node-RED, not the sensor — the divisor was the Sep-2024 calibrated depth 233 cm, but the tank physically tops off rock-steady at ~218 cm every week for 4+ months (per InfluxDB), so full only ever = 93%.

Fix applied: Node-RED node tank 02 : % (id 046d1f81a181a25f), divisor + clamp 233 → 218 (3 occurrences). Single source → propagates to MQTT water/tank/02/percent → sensor.water_tank_02_percentage_basement_k → HA / Grafana / Google Sheets.

Verified live: 191.59 cm now reads 88% (= 191.59/218) vs 82% under old 233.

sensor.water_tank_02_percentage_basement_k is logged to InfluxDB (includes/influxdb.yaml:467, bucket hass, measurement %).

  • Going forward: new points are stored using the new 218-based scale.
  • Historical data is NOT recomputed. InfluxDB keeps the old 233-based values as-written.
  • Result: a step discontinuity of ~+7% in the percentage series at the change timestamp (2026-06-30 ~14:20 +07:00). The same physical level reads ~7% higher after the change (e.g. a true-full tank: 93% before → ~100% after).
  • Unaffected series (calc not changed, no discontinuity): water_tank_02_raw (mm), _cm_, _m_, _capacity_ (L), _capacity_cubicm_ (m³). Capacity = actual volume, independent.

Note: just after the Node-RED reload the moving-average/low-pass buffers reset, so the % (and cm/m) series is briefly more volatile for ~5–10 min, then self-heals.

Update 2026-07-31 — follow-up 1 did NOT pass. The gauge tops out at 92%, because the measured level stepped down 17.39 cm at 2026-06-26 18:39 +07:00 — four days before this recalibration. The 218 divisor was therefore derived from behaviour that had already stopped. The divisor itself is intact and computes correctly; the deficit is upstream (sensor or physical). See 2026-07-31-tank02-level-step-drop.md / #17. The last follow-up below (single-source calibration constant) is now planned as option D in #17.

  • Confirm the gauge reaches ~100% at the next full-fill (~218 cm) on Grafana. Not met — ceiling is 200.6 cm / 92%. Cause tracked in #17.
  • Review any Grafana panel / alert / annotation spanning 2026-06-30 — expect a ~+7% step in the tank-02 % series; add a Grafana annotation at the change time.
  • Re-check any percentage-based thresholds that now mean a slightly different physical level (the % scale shifted up ~7%): tap-water valve setpoints input_number.setpoint_tapwater_tank2_max/min (75/60%) were left unchanged on purpose — valve rarely fires (level usually >75%), low impact, but re-tune if desired.
  • low pass mm/cm caps still 2330 (harmless — above the new 100% point); only the water/tank/02/mm-lowpass MQTT topic is cosmetically off-scale.
  • Optional future hardening: refactor all tank-02 calibration constants to read a single source (Node-RED global or HA input_number) so future recalibration is one edit.
  • Pre-change flows backup on HA host: /addon_configs/a0d7b954_nodered/flows.json.bak-20260630-141727
  • Rollback: sudo cp <bak> /addon_configs/a0d7b954_nodered/flows.json then reload the Node-RED addon via the Supervisor API (NOT docker restart — that hits a mount error and stops the addon):
    TOKEN=$(sudo sh -c 'for p in /proc/[0-9]*/environ; do tr "\0" "\n" < $p 2>/dev/null; done' \
    | grep -m1 '^SUPERVISOR_TOKEN=' | cut -d= -f2)
    curl -s -X POST -H "Authorization: Bearer $TOKEN" http://supervisor/addons/a0d7b954_nodered/restart