PHEC 5-in-1 sensor — Modbus reference (extracted from vendor manuals)
Source: extracted 2026-11-10 from the two vendor PDFs (originals stay in iCloud Downloads):
PHEC五合一传感器 V1.0.docx.pdf(35 p, primary — register map §15–16) andGuide Rail Water Quality Sensor Five-in-One Instruction Manual.docx.pdf(12 p, English, same family). Wiring diagrams are images — see terminal labels on the devices +assembly-guide.md.
Identity & defaults
หัวข้อที่มีชื่อว่า “Identity & defaults”| Item | Value |
|---|---|
| Product | PHEC 5-in-1 rail-mount transmitter (C45 rail), pH + EC + Temp + TDS + Salinity |
| Electrodes | pH (G3/4”, IP68, NTC10K temp comp), EC 2-pole (cell 0.1 / 1.0 / 10.0 cm⁻¹) |
| Power | 9–24 VDC isolated (works ≥6 V), ~25–35 mA |
| Bus | RS485 Modbus-RTU (+ optional 4–20 mA), default address 0x01 |
| Serial defaults | 9600, 8N1 (no parity) |
| Ranges | pH 0–14 (±0.02–0.03) · EC per cell: 200 / 2 000 / 20 000 µS/cm · TDS 0–100/1 000/10 000 ppm · Sal 0–130/1 300/13 000 ppm · Temp 0–60 °C |
| First use note | soak electrode in water, use the next day (accuracy) |
| Install notes | mount in bypass with flow-control valve, vertical, outlet above inlet (avoid bubbles) |
Register map (16-bit integers; signed for negative values)
หัวข้อที่มีชื่อว่า “Register map (16-bit integers; signed for negative values)”| Addr | Hex | PLC | R/W | Meaning | Scaling |
|---|---|---|---|---|---|
| 0 | 0x0000 | 40001 | R | pH | value ÷ 100 (2 dp, 0–14) |
| 1 | 0x0001 | 40002 | R | EC (µS/cm) | per cell constant — 1.0 cell: raw = µS/cm (1 dp-class resolution) |
| 2 | 0x0002 | 40003 | R | Temperature (°C) | value ÷ 10 (1 dp, two’s complement for negatives) |
| 3 | 0x0003 | 40004 | R | TDS (ppm) | per cell constant |
| 4 | 0x0004 | 40005 | R | Salinity (ppm) | per cell constant |
| 48 | 0x0030 | 40049 | R/W | Device address (1–253, default 1) | — |
| 49 | 0x0031 | 40050 | R/W | Baud (0x4800/0x9600/0x1920/0x5760/0x1152) | default 9600 |
| 50 | 0x0032 | 40051 | R/W | Parity 0 none / 1 odd / 2 even | default none |
| 51 | 0x0033 | 40052 | R/W | Auto-report interval (s), 0 = off (sensor pushes frames on RS485) | default off |
| 106 | 0x006A | 40107 | R/W | pH calibration point: 1=4.00, 2=6.86, 3=9.18 | — |
| 127 | 0x007F | 40128 | R/W | EC calibration | — |
Frames (ready to use)
หัวข้อที่มีชื่อว่า “Frames (ready to use)”Read all 5 values (poll): 01 03 00 00 00 05 85 C9
→ reply 01 03 0A [pH×100] [EC] [T×10] [TDS] [SAL] (5 × 16-bit BE) + CRC16
Find a lost address (broadcast): query FE 03 00 30 00 01 90 0A → reply
contains the address. Broadcast 0xFE works with only one slave on the bus.
Change address 1→2: 01 06 00 30 00 02 08 04 (echo = success).
Bench test results — 2026-11-10 evening (unit 1 @ 10.10.10.128)
หัวข้อที่มีชื่อว่า “Bench test results — 2026-11-10 evening (unit 1 @ 10.10.10.128)”Comms verified working (after fixing swapped A/B at the bench): Modbus TCP to
USR :8899 (multi-host mode on), unit 1, fc03. Real readings pulled repeatedly:
pH 9.58–9.65 (electrode dry — expected), Temp 28.2–28.7 °C (true ambient),
EC/TDS/SAL = 0 (electrode in air — physically correct). Values stable across reads.
Empirical findings NOT in the manual:
- count=16 → EXC1 (rejected). count=8 → never answered. count=5 works. The sensor only reliably serves small reads — production must poll with count ≤ 5.
- “Dead windows”: the bus goes silent for minutes at a time (up to 5+ min observed), then answers again — consistent with the sensor’s internal measurement cycle occupying its UART. Request pacing ≥ 10–15 s + retry.
- A USR web-reboot does NOT revive the bus (sensor keeps its 12 V). A full power cycle (sensor included) reliably revives it — the fix that worked twice at the bench. Production implication: needs a stale-data watchdog; consider a switchable outlet for remote recovery.
- USR DR164 multi-host polling (its own 10 s poll) coexists with master reads during live windows; correlation with dead windows is inconclusive — the windows persisted regardless of framing/mode.
Full 0–159 register sweep: not completed — both retry sweeps landed entirely inside dead windows (0/160 twice, then post-reboot hunt failed). Registers 0x0000–0x0004 are verified live; the rest remain per-manual only. Re-run the sweep right after a full power cycle when the window is open (script pattern: probe every 3 s until first reply → burst 32 × count-5 reads).
Recommended production pull (HA, at the real site)
หัวข้อที่มีชื่อว่า “Recommended production pull (HA, at the real site)”modbus: - name: water_quality_1 type: tcp host: <USR_IP> # after moving it to the destination Wi-Fi port: 8899 timeout: 5 retries: 3 # dead-window tolerant sensors: - name: wq1_ph address: 0 input_type: holding scale: 0.01 precision: "2" unit_of_measurement: pH scan_interval: 30 # slow poll — windows + sensor pacing - name: wq1_ec # address 1, µS/cm (scale 1) - name: wq1_temp # address 2, scale 0.1, °C - name: wq1_tds # address 3, ppm - name: wq1_salinity # address 4, ppmPlus a Node-RED/template watchdog: no fresh value > 5 min → alert (and note the recovery action = power-cycle the box).
Unit 2 (10.10.11.250): bus dead in BOTH A/B orientations, all unit IDs 1–16 + broadcast, across reboots — USR side verified identical/correct. Pending owner’s multimeter check (12 V at V+/V−, wires on RS485 terminals); if both pass ⇒ sensor DOA — claim/replace before customer delivery.
Integration options for RILF (decision pending owner)
หัวข้อที่มีชื่อว่า “Integration options for RILF (decision pending owner)”The sensor is RS485-only — any IP access goes through the USR-DR164/162
gateway (its web UI is what’s running at http://10.10.10.128/ on the
bench LAN during testing — not the OBH 194.1.x network).
| # | Path | How | Best for |
|---|---|---|---|
| 1 | Modbus TCP gateway | USR in Modbus-TCP↔RTU mode → HA modbus integration polls 10.10.10.128:502 (prod: OBH IP), registers 0x0000–0x0004 |
ทดสอบ/production ที่ HA อ่านเอง — ง่ายและตรง |
| 2 | MQTT | USR MQTT mode + built-in Modbus poll → publish JSON to broker (prod: Mosquitto 194.1.0.1:1883) → HA MQTT sensors (RUGON pattern) |
production ใน OBH — สอดคล้องสถาปัตยกรรมเดิม |
| 3 | TCP transparent + Node-RED | raw socket ↔ RS485; Node-RED builds/parses RTU frames | ต้องการ logic พิเศษ (เช่น รวม cal/คำนวณก่อน publish) |
| 4 | HTTP scrape of the USR web page | poll http://…/ |
ทดสอบเท่านั้น |
Bonus: sensor register 0x0033 can make the sensor itself push every N s (auto-report), so option 3 could be push-style instead of polled.
Before production: move the USR onto the destination Wi-Fi (OBHIoT → 194.1.1.x) — 10.10.10.x is bench-only; then apply the same broker/ACL pattern as other site devices.