| No |
Model |
Building |
IP |
Data Logger |
Connection |
| 1 |
SUN2000-60KTL-M0 (x2) |
K (อาคารหมอกัมพล) |
194.1.1.1 |
EW11 + Waveshare |
Modbus TCP, Slave ID=1 |
| 2 |
SUN2000-60KTL-M0 |
B (อาคารหมอบริกส์) |
194.1.1.2 |
Waveshare |
Modbus TCP, Slave ID=1 |
| 3 |
SUN2000-20KTL-M5 |
HN (หอพัก/Dormitory) |
194.1.1.3 |
Waveshare |
Modbus TCP, Logical Address=2 |
Note: SmartLogger 3000 #3 (Building HN) uses Logical Address=2 to allow Inverter D data retrieval via Address=1 (changed Aug 2024).
| Device |
IP |
SSID |
Type |
Connected To |
| Solar Logger #1/1 |
194.1.3.246 |
- |
EW11 (RS485-WiFi) |
Inverter K-1 |
| Solar Logger #1/2 |
194.1.1.119 |
Waveshare_6A44 |
Waveshare |
Inverter K-2 |
| Solar Logger #2 |
194.1.1.120 |
Waveshare_05B4 |
Waveshare |
Inverter B |
| RS485 Logger #1 |
194.1.1.153 |
Inverter-K1 |
Waveshare |
Inverter K-1 |
| RS485 Logger #4 |
194.1.1.154 |
RS485_04 |
Waveshare |
Building D |
| RS485 Logger #5 |
194.1.1.155 |
RS485_05 |
Waveshare |
- |
| RS485 Logger #6 |
194.1.1.156 |
RS485_06 |
Waveshare |
- |
The EW11 (Elfin-brand) bridge connects Huawei SUN2000 inverters to the network:
| Parameter |
Value |
| Network Mode |
DHCP (static fallback: 10.10.100.10) |
| WiFi Mode |
AP+STA (STA connects to OBHIoT, AP broadcasts EW11_8F1A) |
| UART/RS485 |
9600 baud, 8N1, half-duplex |
| Protocol |
Modbus RTU, 4096-byte buffer, 50ms gap time |
| TCP Socket |
Server on port 8899, max 3 connections, keepalive 120s |
Huawei SmartLogger3000 installed for solar data aggregation:
- Interfaces: RS485 (multiple terminal blocks), LAN, MBUS L3, 4G cellular (SMA antenna)
- I/O: DI (digital input), AI (analog 0-10V / 4-20mA), DO (relay NC/COM/NO)
- Power: DC 24V
- Reference Docs: SUN2000 user manuals (50KTL, 60KTL, 8-20KTL-M2), Modbus Interface Definitions
| Device |
Location |
IP |
Source |
| EMON 3P #1 |
UPS อาคารหมอกัมพล |
194.1.1.117 |
UPS Power |
| EMON 3P #2 |
UPS อาคารหมอบริกส์ |
194.1.1.118 |
UPS Power (ตู้ Main) |
| EMON 3P #3 |
MDB-K1 |
194.1.1.150 |
MDB Power |
| EMON 3P #4 |
MDB-K2 |
194.1.1.151 |
MDB Power |
| EMON 3P #5 |
MDB-B1 |
194.1.1.152 |
MDB Power |
- CT clamp installation: Thread cables from inside the electrical cabinet
| Metric |
Unit |
Entity Pattern |
Notes |
| Current (3-phase) |
A |
sensor.obh_emon3p_{nn}_energy_current_{0,1,2} |
Per phase |
| Power (3-phase) |
W |
sensor.obh_emon3p_{nn}_energy_power_{0,1,2} |
Per phase |
| Voltage (3-phase) |
V |
sensor.obh_emon3p_{nn}_energy_voltage_{0,1,2} |
Stored but not primary |
| Energy Today |
kWh |
sensor.obh_emon3p_{nn}_energy_today |
Daily consumption |
| Energy Yesterday |
kWh |
sensor.obh_emon3p_{nn}_energy_yesterday |
Previous day |
| Energy Total |
kWh |
sensor.obh_emon3p_{nn}_energy_total |
Cumulative |
| Energy Monthly |
kWh |
sensor.obh_emon3p_{nn}_energy_monthly |
Manual calculated sensor |
All energy data is stored in InfluxDB and visualized in Grafana.
| Type |
Qty |
CT Type |
Price/Unit |
| 3-Phase Energy Monitor |
4 |
Split Core CT |
~16,250 THB |
| 3-Phase Energy Monitor |
14 |
Rogowski/Flexible CT |
~17,200 THB |
| Implementation & Integration |
1 lot |
- |
~51,400 THB |
Connection via RS485. (มูลค่าและเลขอ้างอิง PO/DN — ดูในเอกสารจัดซื้อของโรงพยาบาล; redacted 2026-11-20)
This brings total energy monitors from 5 to 23 across the hospital.
| UPS |
Building |
IP |
SNMP |
| OBH-UPS-01 |
อาคารหมอบริกส์ |
194.1.1.50 |
Yes |
| OBH-UPS-02 |
อาคารหมอกัมพล |
194.1.1.51 |
Yes |
| OBH-UPS-03 |
ระบบงานรังสี (X-Ray) |
194.1.1.52 |
Yes (different OIDs) |
| OBHMS-UPS-01 |
คลินิกแม่สาย |
194.2.1.50 |
Yes |
| OBHCK-UPS-01 |
คลินิกเชียงของ |
194.3.1.50 |
Yes |
All UPS data flows: SNMP -> Home Assistant -> InfluxDB -> Grafana